Abstract
This study discusses how to improve energy performance standards for vapour compression chillers. A review on the national standards adopted in the USA, Canada, Australia, the European Union, China, Chinese Taipei and Hong Kong showed that minimum allowable levels are simply stated for the coefficient of performance (COP) of chillers at full load conditions. These requirements are insufficient to promote high efficient products. To facilitate the labelling and certification of high efficient chillers, it is more preferable to have a classification scheme for the full load COP. Such a scheme has been adopted in the European and Chinese standards. Yet the minimum COP for each class needs to be fine-tuned based on a comprehensive range of chiller products. While the American-based ASHRAE standard sets out the minimum integrated part load value (IPLV) to specify the minimum COP of chillers at part load operation, it is inadequate to use the IPLV to present the actual chiller performance under diverse building cooling load and climate conditions. The significance of this paper is to highlight a pragmatic rating method which specifies precisely the part load performance of chillers and to address the ways of properly developing minimum COP levels for chillers at part load operation.
| Original language | English |
|---|---|
| Title of host publication | IAQVEC 2007 Proceedings - 6th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings |
| Subtitle of host publication | Sustainable Built Environment |
| Pages | 75-82 |
| Number of pages | 8 |
| Publication status | Published - 2007 |
| Event | 6th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings: Sustainable Built Environment, IAQVEC 2007 - Sendai, Japan Duration: 28 Oct 2007 → 31 Oct 2007 |
Publication series
| Name | IAQVEC 2007 Proceedings - 6th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings: Sustainable Built Environment |
|---|---|
| Volume | 2 |
Conference
| Conference | 6th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings: Sustainable Built Environment, IAQVEC 2007 |
|---|---|
| Country/Territory | Japan |
| City | Sendai |
| Period | 28/10/07 → 31/10/07 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- ARI standard 550/590
- Coefficient of performance
- Part load rating
Fingerprint
Dive into the research topics of 'Improved energy efficiency standards for vapour compression chillers serving buildings'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver